地鐵35 kV環(huán)網(wǎng)數(shù)字通信電流保護測試方法

2019-06-19 12:39:04陳繼勇徐文亮
城市軌道交通研究 2019年6期
關(guān)鍵詞:數(shù)字通信環(huán)網(wǎng)過流

陳繼勇 徐文亮 鄭 杰

(成都地鐵運營有限公司,610058,成都∥第一作者,工程師)

地鐵35 kV中壓環(huán)網(wǎng)數(shù)字通信電流保護能適應(yīng)多級串行供電系統(tǒng),具有“絕對選擇性”,解決了傳統(tǒng)保護的級差配合難題,適應(yīng)地鐵實際運行環(huán)境,可有效實現(xiàn)地鐵中壓環(huán)網(wǎng)大分區(qū)供電。其在供電方式調(diào)整時能自動適應(yīng)“正常供電”和“支援供電”兩種運行方式,保護定值不再需要進(jìn)行調(diào)整,為地鐵線路快速恢復(fù)供電提供了有力保障。此外,數(shù)字通信電流保護的優(yōu)越性也對校驗保護方案的完整性提出了更高的要求。如何對新建線路中壓環(huán)網(wǎng)數(shù)字通信電流保護進(jìn)行全面測試校驗,為地鐵開通運營保駕護航,是研究此項技術(shù)現(xiàn)場應(yīng)用的關(guān)鍵。

1 數(shù)字通信電流保護的實現(xiàn)原理

地鐵交流供電系統(tǒng)采用環(huán)網(wǎng)供電方式,每個變電所設(shè)置環(huán)網(wǎng)進(jìn)出線開關(guān)柜,并在進(jìn)出線開關(guān)柜設(shè)置線網(wǎng)電纜及母線保護。如圖1所示,數(shù)字通信電流保護常用近區(qū)加速實現(xiàn),采用雙差動保護形式,即后備保護裝置也兼具差動功能。站內(nèi)進(jìn)、出線柜后備保護裝置用硬接線連接,傳遞故障定位a信號;站間差動保護及后備保護裝置用光纖連接,傳遞過流同步開放信號。正常運行過程中過流Ⅲ段永久運行,過流Ⅰ段處于閉鎖狀態(tài),通過a信號判斷是否開放過流Ⅰ段。在后備保護中,定義內(nèi)部故障定位信號a,當(dāng)本柜后備保護裝置差動未啟動且檢測到大電流時定義a=1,反之a(chǎn)=0。本柜a=1且對側(cè)后備裝置a=0時解鎖本柜過流Ⅰ段。同時通過后備光纖通道將過流開放信息發(fā)送至對端開關(guān)柜,開放對端后備裝置過流Ⅰ段,成為下級站開關(guān)失靈的后備保護。所內(nèi)饋線及母聯(lián)保護裝置不參與數(shù)字通信,通過常規(guī)時間級差實現(xiàn)保護選擇性,動態(tài)級差確保不越級動作。當(dāng)供電方向發(fā)生改變時,進(jìn)、出線柜功能互換,保護功能不變,故障定位信號自動與之匹配,鎖定故障范圍。

2 測試技術(shù)

傳統(tǒng)的繼電保護測試儀主要應(yīng)用于供電系統(tǒng)中單體設(shè)備單裝置保護功能的精準(zhǔn)校驗,在電力系統(tǒng)及地鐵供電系統(tǒng)應(yīng)用極為廣泛。目前國內(nèi)主流品牌的繼電保護測試儀售價為15萬~20萬元不等。隨著數(shù)字通信電流保護技術(shù)在地鐵環(huán)網(wǎng)供電系統(tǒng)的廣泛應(yīng)用,其保護實現(xiàn)原理決定了保護校驗的特殊性,而傳統(tǒng)的繼電保護測試儀無法實現(xiàn)多臺設(shè)備聯(lián)機同步輸出功能,不能對數(shù)字通信電流保護進(jìn)行全面的測試校驗。

由于數(shù)字通信電流保護的選擇性涉及多個變電所邏輯的同步判斷,任一環(huán)節(jié)出錯將導(dǎo)致供電分區(qū)內(nèi)出現(xiàn)越級跳閘,所以實現(xiàn)邏輯功能的完整校驗是數(shù)字通信電流保護得以可靠應(yīng)用的關(guān)鍵??紤]到地鐵變電所所屬地下環(huán)境以及保護方法的差異性,基于GPS(全球定位系統(tǒng))、光纖B碼等對時技術(shù)的多站同步輸出測試儀,為數(shù)字通信電流保護校驗提供了新的測試思路。新型的繼電保護測試儀在傳統(tǒng)測試儀的基礎(chǔ)上集成配置了對時模塊,僅增加約5 000~8 000元的費用,便可以實現(xiàn)多機同步輸出功能;同時可充分利用地鐵環(huán)網(wǎng)特有的站間差動預(yù)留光纖,實現(xiàn)繼電保護測試儀多站同步信號發(fā)送接收,從而解決了環(huán)網(wǎng)供電系統(tǒng)站間同步聯(lián)調(diào)的難題。

圖1 環(huán)網(wǎng)進(jìn)出線開關(guān)柜保護配置圖

3 測試方法

多站同步加量測試可完全模擬實際運營期間的各類型環(huán)網(wǎng)故障點位,以單元化的測試思路,在多站保護裝置進(jìn)行故障邏輯同步判斷,從而實現(xiàn)保護邏輯站內(nèi)、站間的同步校驗。

現(xiàn)場測試以地鐵A、B、C三站同Ⅰ(Ⅱ)段母線為測試單元,A、B站放置同步加量測試儀器。利用站間預(yù)留的差動光纖實現(xiàn)模塊時鐘同步,通過設(shè)定統(tǒng)一輸出時間實現(xiàn)繼電保護測試儀同步加量。測試順序以主變電所或開閉所電源出線為測試起點A站,測試主站為B站,逐站推進(jìn);每一座變電站均在測試過程中成為主站。

結(jié)合當(dāng)前保護原理及測試方法,本文對典型故障實際測試方法及邏輯判斷進(jìn)行分析。

3.1 BC站間環(huán)網(wǎng)故障

如圖2所示,測試時,在A站103開關(guān)柜(以下簡為103,余類同)加故障電流I,時長0.4 s,硬線開入模擬103收到站內(nèi)101的a=1信號;在B站101和103加故障電流I,時長0.4 s。

圖2 區(qū)間環(huán)網(wǎng)故障示意圖

觀察分析B站103和C站101的差動裝置、后備裝置差動是否同時動作。B站103差動啟動且有大電流a=0,B站101差動未啟動且有大電流a=1,因此101開放過流Ⅰ段,同時軟件開放A站103過流Ⅰ段。模擬A站103收到站內(nèi)101發(fā)出的a=1信號,上級站接收到大電流且差動未啟動的信息,即表明來電方向在A站。因測試加量時間0.4 s,即可模擬B站103和C站101的差動裝置、后備裝置差動動作已將故障可靠切除。A站103和B站101過流Ⅰ段保護出口延時未達(dá)到,保護立即返回。模擬B站斷路器失靈,測試方法同上,通過對調(diào)整加量時長至0.6 s,模擬B站103切除故障失敗,由后備保護A站103和B站101過流I段動作出口跳閘。

3.2 B站母線故障

如圖3所示,測試時在A站103加故障電流I,時長0.6 s,硬線開入模擬103收到站內(nèi)101的a=1信號;在B站101和103加故障電流I,時長0.6 s。

103過流Ⅰ段開放邏輯分析過程同BC環(huán)網(wǎng)故障。因測試加量時間0.6 s,即模擬A站103和B站101過流Ⅰ段動作出口跳閘。因A站103和B站101過流Ⅰ段保護同步開放,當(dāng)B站101斷路器失靈后故障點仍可通過A站103予以可靠切除。

圖3 站內(nèi)母線故障示意圖

3.3 B站饋線故障

如圖4所示,測試時在A站103加故障電流I,時長0.25 s,硬線開入模擬103收到站內(nèi)101的a=1信號;在B站101和111加故障電流I,時長0.25 s。

B站101和A站103過流I段開放邏輯分析同BC環(huán)網(wǎng)故障。因測試加量時間0.25 s,即模擬B站111過流保護動作出口跳閘。因A站103和B站101過流I段保護同步開放,當(dāng)B站111斷路器失靈,故障點仍通過A站103和B站101同步可靠切除。

圖4 站內(nèi)饋線故障示意圖

圖5 站內(nèi)II段母線故障示意圖

3.4 B站Ⅰ母支援Ⅱ母供電,Ⅱ母故障

如圖5所示,測試時在A站103加故障電流I,時長0.4 s,硬線開入模擬103收到站內(nèi)101的a=1信號;在B站101和110加故障電流I,時長0.4 s。

B站101和A站103過流I段開放邏輯測試分析同BC環(huán)網(wǎng)故障。因測試加量時間0.4 s,即模擬B站110過流保護動作已將故障切除。A站103和B站101過流I段動作延時未達(dá)到立即返回。模擬B站母聯(lián)110斷路器失靈,測試方法不變,通過對調(diào)整加量時長至0.6 s,模擬B站母聯(lián)110切除故障失敗,由A站103和B站101過流I段動作出口跳閘。

4 結(jié)語

供電系統(tǒng)是地鐵新線建設(shè)的先頭工程和重點工程。一旦環(huán)網(wǎng)帶電,各專業(yè)調(diào)試將全面展開,再次大面積停電調(diào)試將嚴(yán)重影響其他專業(yè)的調(diào)試工作。因此,應(yīng)充分把握環(huán)網(wǎng)保護調(diào)試時間,系統(tǒng)性地驗證各保護動作的關(guān)鍵故障點。為使環(huán)網(wǎng)保護能得以成功應(yīng)用,離不開與之匹配的測試方法,應(yīng)充分發(fā)掘利用新技術(shù)、新設(shè)備來打破傳統(tǒng)的測試思路。多站同步加量測試技術(shù)在地鐵供電系統(tǒng)的成功應(yīng)用,從系統(tǒng)安全運行的角度來分析模擬故障點位的發(fā)生,通過全面性的功能驗證,保證了地鐵中壓環(huán)網(wǎng)供電系統(tǒng)的可靠穩(wěn)定運行,進(jìn)而為地鐵運營提供最有力的保障。

(收稿日期:2017-08-21)

(Continued from Commentary)

aging and generating a lot of failures,which need to be overhauled and refurbished.When it comes to signaling,due to the limitations of system mode,i.e.track circuit or intermittent ATP,or the aging of the existing system,the demand of ever growing ridership can no longer be efficiently fulfilled.

The modernization of an existing line is more complex than building a new line and faces multiple challenges.For example,we have to ensure the operation of the existing line and take the new system into consideration to allow for interfaces.Technical solutions may vary as cities are different from each other in terms of network,ridership,and signaling system.Globally speaking,in UK where the world′s earliest metro was built,the London 4 LM (Lines mondernization) is the world′s most complicated modernization project.In China,Shanghai Line 5 is the first urban rail line where operation,renovation,and construction were fulfilled at the same time.

The difficulty of resignaling resides in two aspects.Firstly,the new system replacing the old one should be as robust as the system for a new line.However,due to the constraints of the infrastructure of the existing line,many issues have to be tackled creatively.Secondly,resignaling cannot impact service or should at least keep the impact to the minimum.As there are many times of switchovers between the old and the new system,we have to ensure both safety and efficiency of commissioning.This makes it even more demanding fro system development,site deployment,and construction planning.Take Shanghai Line 5 for example.The line was originally opened in 2003.The equipment was aging and the intermittent ATP system could no longer meet the requirement of ever increasing ridership.The resignaling of Shanghai Line 5 includes not only the replacement of the the signaling system but also adding 6-car trains to run in mixed operation with the existing 4-car trains,as well as the installation of platform screen doors and renovation of auxiliary tracks.In the meanwhile,the south extension was carried out.The resignaling should have no impact on the service of the existing line.TST′s local innovation TSTCBTC?2.0 was selected for Shanghai Line 5.The system′s dual CBTC architecture enhances the core functions of signaling and helps achieve higher availability.Less wayside equipment is required,which reduces the conflict of space for outdoor facilities and suits the reality of opening in different sections and in different time.With no service disruption,the cutover between the old and new signaling system was successfully completed in Oct,2018 after more than 500 days of commissioning and over 1 000 switchovers.By the end of 2018,Shanghai Line 5 went into full line service.

The network of urban rail transport in China′s mega cities and big cities is becoming more and more mature.We are expecting fewer new lines in the future,whilst modernization of existing lines will become the new normal.Besides Shanghai,Tianjin,Dalian,Chongqing,and Guangzhou either have lines modernized or are planning for it.For urban rail operators and system integrators,it is an all-time focus of safe and efficient operation.How to ensure continuous operation with a highly available system and how to upgrade the system through highly safe modernization with little risk are what we all need to think about.The resignaling and south extension of Shanghai Line 5 made many ground-breaking achievements,providing a lot of experience that can be shared to the industry.This also sets the stage for the standardization of urban rail modernization in China.

猜你喜歡
數(shù)字通信環(huán)網(wǎng)過流
數(shù)字通信&數(shù)學(xué)
基于ODUk Spring方式實現(xiàn)基礎(chǔ)網(wǎng)絡(luò)環(huán)網(wǎng)保護的研究
數(shù)字通信系統(tǒng)中自適應(yīng)均衡技術(shù)
高速公路萬兆環(huán)網(wǎng)建設(shè)探析
變壓器相間過流保護不正確動作原因的探討
電子制作(2017年19期)2017-02-02 07:08:58
國產(chǎn)500kW短波發(fā)射機過流保護電路的應(yīng)用缺陷與改進(jìn)
電子制作(2016年11期)2016-11-07 08:43:36
水輪機過流部件改造與節(jié)能增效
基于CAN的冗余控制及其在軌道交通門禁環(huán)網(wǎng)中的應(yīng)用
配網(wǎng)雙端閉鎖式過流保護的實現(xiàn)方法
萬兆環(huán)網(wǎng)在京秦高速智能化監(jiān)控中的應(yīng)用
威远县| 台州市| 徐闻县| 富顺县| 广东省| 安丘市| 周宁县| 无锡市| 航空| 富顺县| 池州市| 湟源县| 新乡县| 盐亭县| 曲麻莱县| 嵩明县| 三门县| 即墨市| 镇康县| 黔南| 万全县| 通化市| 潢川县| 偃师市| 集贤县| 康平县| 灵石县| 隆子县| 安仁县| 红桥区| 夏邑县| 连江县| 微博| 德庆县| 藁城市| 临沭县| 托克逊县| 宣威市| 渭源县| 兰溪市| 珲春市|